Corresponding Author

Abdel Aziem, Kamal

Subject Area

Electrical Engineering

Article Type

Original Study

Abstract

The objective of this paper is to present an approach for isolating the harmonic contents in both voltage and current waveforms of the montage feeder of Gharb Talkha substation (60/11 KV). A novel technique using Discrete Wavelet transform (DWT) for the analysis of the waveforms harmonics content At the beginning the substation is simulated using Simulink toolbox in Matlab program with and without the presence of capacitor bunk. The obtained voltage and current waveforms are compared to the actual data. The proposed model is used to study the effect of replacing the capacitor bank with single tuned parallel passive filter. The resulting current and voltage waveforms are analyzed using the proposed DWT technique. The analysis showed that the Total Harmonic Distortion (THD) of both voltage and current waveforms is improved as well as the power factor.

Keywords

Discrete Wavelet Transform (DWT); Harmonic Elimination; Total Harmonic Distortion (THD). and distribution power system

Share

COinS