Subject Area
Electrical Engineering
Article Type
Original Study
Abstract
This paper presents a modelling and experimental verification system for a group of induction motors during starting in medium voltage networks including its effects on other nearby running units in different operating conditions. The simulation model is based on a real-life case study which is an agricultural drain pump station. The dynamic model was built with MATLAB®/SIMULINK® where a thorough performance analysis can be achieved. For system verification, the simulation curve results were compared with real-life data curves which were recorded by a suitable device located on worksite. The verified model was used to perform six practical scenarios based on the real station’s operating instructions. For each studied scenario, a group of parameters such as voltage dip, its duration and voltage regulation are discussed in detail and compared in a tabular form considering the recommended adjustments for the protection relay settings
Keywords
Induction motor; Transient state; dynamic model
Recommended Citation
El-Hayes, Mahmoud; Gouda, Eid; Abdelkader, Sobhy; and Abdulsalam, Gabr
(2020)
"Practical Transient State Assessment for Induction Motors Starting in Medium Voltage Networks.,"
Mansoura Engineering Journal: Vol. 44
:
Iss.
2
, Article 2.
Available at:
https://doi.org/10.21608/bfemu.2020.95019