Subject Area
Mechanical Power Engineering
Article Type
Original Study
Abstract
Decreasing the heat rejection of any power cycle is a promising agent in improving the overall performance and decreasing global warming. This can be done by different methods such as heat exchangers or thermosyphons. Water is used as a working fluid. The present experimental work used water as a working fluid and investigated the effects of filling ratio (27.2%≥Fr≥9%), total nozzle exit area to the turbine inlet area (4.3%≥Ar≥2.5%), and condenser cooling water flow rate (16LPM≥(V ̇) ̇≥8LPM). The results showed that the optimum-filling ratio is approximately 13.6% and the output power increases with increasing condenser cooling water flow rate. Also, the maximum output power produced at minimum area ratio but the optimum turbine rotational speed at area ratio of 3.1%. In addition, the maximum output power without load from the present turbine is 5.28 W at Fr= 13.6 %, Ar=2.5% and V ̇=16 LPM
Keywords
Thermosyphon; Rankine turbine; low temperature; revolution per minute
Recommended Citation
Habieeb, Abed; Sultan, Gamal; Awad, Mohamed; and Elshmouty, Ahmed
(2020)
"An Experimental Study of a Two-Phase Closed Thermosyphon Rankine Cycle Performance.,"
Mansoura Engineering Journal: Vol. 45
:
Iss.
1
, Article 4.
Available at:
https://doi.org/10.21608/bfemu.2020.89188