Abstract

An algorithm for calculating the apparent transmission line impedance to the point of fault is presented. This algorithm is based on a half-cycle Window using walsh function technique. The real and the imaginary components of the fundamental frequency voltage and current of the faulty phases are evaluated and used to calculate the impedance, as seen from the relay location. The sampling rate used to test this algorithm is 16 samples/cycle. The algorithm has been tested using digital computer simulation of the sample model. A comparison between this algorithm and four other algorithms, suitable for fault impedance measurement was carried on here with particular reference to their accuracy and speed of calculations.